6. Operation
S
3
L Terminals
Connect “input” directly to the S
3
L instrument.
Connect an S
3
L sensor to “pass-thru” for convenience.
Indicator LEDs
DATA On when S
3
L serial data is transmitted,
or when a relay is in TEST mode.
POWER On when input power is connected to 8059
Relay A On when Relay A is energized
Relay B On when Relay B is energized
Relay C On when Relay C is energized
Relay D On when Relay D is energized
Test Buttons
Test A Press to manually control Relay A
Test B Press to manually control Relay B
Test C Press to manually control Relay C
Test D Press to manually control Relay D
Relays
The 250V/5A dry-contact relays are controlled via the serial
connection to the instrument. Use NO (normally open), COM
(common) and NC (normally closed) to control external
equipment.
Normal Operation:
Green COM LED ickering rapidly.
Both relays are controlled by the host instrument.
8. Ordering Information
3-8059-4 159 000 772 External 4-Relay Module
3-8059-4AC 159 000 773 External 4-Relay Module with power supply
3-8050.396 159 000 617 RC Filter Kit
6205-0002 159 000 858 DIN Rail, 1m
6205-0003 159 000 859 End Clips, DIN Rail
NC C NO
RELAY A
NC C NO
RELAY B
NC C NO
RELAY C
NC C NO
RELAY D
+
S
3
L
-
+
S
3
L
-
OUTPUT 24VDC
+ -
AC INPUT
INPUT
PASS-THRU
L N
COM
POWER
Signet 3-8059 Relay Module
Test A
Test B
Test C
Test D
Relay A
Relay B
Relay C
Relay D
LISTED
E171559
®
7. Relay Test
NOTE: The 8059 will automatically return to normal operation if no buttons are pressed for 5 minutes.
8059-4
8059-4AC
Action 8059 Response
Press and hold TEST button for 5 seconds (until
green DATA LED begins to blink slowly)
The selected relay is now controlled by the TEST button.
Pressing the other relay TEST button has no effect.
Momentarily press TEST button to toggle relay.
The red RELAY LED will toggle to indicate relay condition.
To return relay to Normal Operation:
Press and hold the TEST button for 5 seconds
(until green DATA light begins to icker rapidly)
The relay returns to active status, controlled by the host
instrument.